NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 40 Amps at 100 Feet (240V)?

For a 40-amp circuit running 100 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 8 AWG copper (2.6% voltage drop) or 6 AWG aluminum (2.69% voltage drop).

Recommended Copper Wire
8 AWG
Voltage drop: 2.6% · 75°C rating: 50A
Recommended Aluminum Wire
6 AWG
Voltage drop: 2.69% · 75°C rating: 50A
Minimum Circular Mils (Cu)
14,333 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
8 AWG Copper
Copper Voltage Drop2.6%
Aluminum Alternative6 AWG
Aluminum Voltage Drop2.69%

Frequently Asked Questions — 40A · 100 ft (240V)

What size copper wire do I need for 40 amps at 100 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 8 AWG copper wire for a 40-amp, 100-foot one-way run at 240V. This produces an estimated 2.6% voltage drop.

Can I use aluminum wire for 40 amps at 100 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 40A at 100 ft (240V), step up to 6 AWG aluminum conductor (2.69% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 8 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 40 Amps (240V)

40A @ 25 ft40A @ 50 ft40A @ 75 ft40A @ 100 ft40A @ 125 ft40A @ 150 ft40A @ 200 ft40A @ 250 ft40A @ 300 ft40A @ 400 ft

Other Amperages at 100 Feet (240V)

15A @ 100 ft20A @ 100 ft30A @ 100 ft40A @ 100 ft50A @ 100 ft60A @ 100 ft70A @ 100 ft80A @ 100 ft100A @ 100 ft125A @ 100 ft150A @ 100 ft200A @ 100 ft