What Size Wire for 15 Amps at 150 Feet (240V)?
For a 15-amp circuit running 150 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 10 AWG copper (2.33% voltage drop) or 8 AWG aluminum (2.41% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 15A · 150 ft (240V)
What size copper wire do I need for 15 amps at 150 feet (240V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 10 AWG copper wire for a 15-amp, 150-foot one-way run at 240V. This produces an estimated 2.33% voltage drop.
Can I use aluminum wire for 15 amps at 150 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 15A at 150 ft (240V), step up to 8 AWG aluminum conductor (2.41% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 10 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.