NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 60 Amps at 150 Feet (240V)?

For a 60-amp circuit running 150 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 4 AWG copper (2.32% voltage drop) or 2 AWG aluminum (2.4% voltage drop).

Recommended Copper Wire
4 AWG
Voltage drop: 2.32% · 75°C rating: 85A
Recommended Aluminum Wire
2 AWG
Voltage drop: 2.4% · 75°C rating: 90A
Minimum Circular Mils (Cu)
32,250 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4 AWG Copper
Copper Voltage Drop2.32%
Aluminum Alternative2 AWG
Aluminum Voltage Drop2.4%

Frequently Asked Questions — 60A · 150 ft (240V)

What size copper wire do I need for 60 amps at 150 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4 AWG copper wire for a 60-amp, 150-foot one-way run at 240V. This produces an estimated 2.32% voltage drop.

Can I use aluminum wire for 60 amps at 150 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 60A at 150 ft (240V), step up to 2 AWG aluminum conductor (2.4% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.