What Size Wire for 60 Amps at 25 Feet (240V)?
For a 60-amp circuit running 25 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 6 AWG copper (0.61% voltage drop) or 4 AWG aluminum (0.63% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 60A · 25 ft (240V)
What size copper wire do I need for 60 amps at 25 feet (240V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 6 AWG copper wire for a 60-amp, 25-foot one-way run at 240V. This produces an estimated 0.61% voltage drop.
Can I use aluminum wire for 60 amps at 25 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 60A at 25 ft (240V), step up to 4 AWG aluminum conductor (0.63% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 6 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.