NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 20 Amps at 25 Feet (240V)?

For a 20-amp circuit running 25 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 12 AWG copper (0.82% voltage drop) or 10 AWG aluminum (0.85% voltage drop).

Recommended Copper Wire
12 AWG
Voltage drop: 0.82% · 75°C rating: 20A
Recommended Aluminum Wire
10 AWG
Voltage drop: 0.85% · 75°C rating: 25A
Minimum Circular Mils (Cu)
1,792 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
12 AWG Copper
Copper Voltage Drop0.82%
Aluminum Alternative10 AWG
Aluminum Voltage Drop0.85%

Frequently Asked Questions — 20A · 25 ft (240V)

What size copper wire do I need for 20 amps at 25 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 12 AWG copper wire for a 20-amp, 25-foot one-way run at 240V. This produces an estimated 0.82% voltage drop.

Can I use aluminum wire for 20 amps at 25 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 20A at 25 ft (240V), step up to 10 AWG aluminum conductor (0.85% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 12 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.