NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 60 Amps at 125 Feet (240V)?

For a 60-amp circuit running 125 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 4 AWG copper (1.93% voltage drop) or 3 AWG aluminum (2.52% voltage drop).

Recommended Copper Wire
4 AWG
Voltage drop: 1.93% · 75°C rating: 85A
Recommended Aluminum Wire
3 AWG
Voltage drop: 2.52% · 75°C rating: 75A
Minimum Circular Mils (Cu)
26,875 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4 AWG Copper
Copper Voltage Drop1.93%
Aluminum Alternative3 AWG
Aluminum Voltage Drop2.52%

Frequently Asked Questions — 60A · 125 ft (240V)

What size copper wire do I need for 60 amps at 125 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4 AWG copper wire for a 60-amp, 125-foot one-way run at 240V. This produces an estimated 1.93% voltage drop.

Can I use aluminum wire for 60 amps at 125 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 60A at 125 ft (240V), step up to 3 AWG aluminum conductor (2.52% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 60 Amps (240V)

60A @ 25 ft60A @ 50 ft60A @ 75 ft60A @ 100 ft60A @ 125 ft60A @ 150 ft60A @ 200 ft60A @ 250 ft60A @ 300 ft60A @ 400 ft

Other Amperages at 125 Feet (240V)

15A @ 125 ft20A @ 125 ft30A @ 125 ft40A @ 125 ft50A @ 125 ft60A @ 125 ft70A @ 125 ft80A @ 125 ft100A @ 125 ft125A @ 125 ft150A @ 125 ft200A @ 125 ft