NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 20 Amps at 75 Feet (120V)?

For a 20-amp circuit running 75 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 8 AWG copper (1.95% voltage drop) or 6 AWG aluminum (2.02% voltage drop).

Recommended Copper Wire
8 AWG
Voltage drop: 1.95% · 75°C rating: 50A
Recommended Aluminum Wire
6 AWG
Voltage drop: 2.02% · 75°C rating: 50A
Minimum Circular Mils (Cu)
10,750 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
8 AWG Copper
Copper Voltage Drop1.95%
Aluminum Alternative6 AWG
Aluminum Voltage Drop2.02%

Frequently Asked Questions — 20A · 75 ft (120V)

What size copper wire do I need for 20 amps at 75 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 8 AWG copper wire for a 20-amp, 75-foot one-way run at 120V. This produces an estimated 1.95% voltage drop.

Can I use aluminum wire for 20 amps at 75 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 20A at 75 ft (120V), step up to 6 AWG aluminum conductor (2.02% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 8 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.