NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 30 Amps at 75 Feet (120V)?

For a 30-amp circuit running 75 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 8 AWG copper (2.93% voltage drop) or 4 AWG aluminum (1.9% voltage drop).

Recommended Copper Wire
8 AWG
Voltage drop: 2.93% · 75°C rating: 50A
Recommended Aluminum Wire
4 AWG
Voltage drop: 1.9% · 75°C rating: 65A
Minimum Circular Mils (Cu)
16,125 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
8 AWG Copper
Copper Voltage Drop2.93%
Aluminum Alternative4 AWG
Aluminum Voltage Drop1.9%

Frequently Asked Questions — 30A · 75 ft (120V)

What size copper wire do I need for 30 amps at 75 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 8 AWG copper wire for a 30-amp, 75-foot one-way run at 120V. This produces an estimated 2.93% voltage drop.

Can I use aluminum wire for 30 amps at 75 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 30A at 75 ft (120V), step up to 4 AWG aluminum conductor (1.9% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 8 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.