NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 30 Amps at 300 Feet (120V)?

For a 30-amp circuit running 300 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 2 AWG copper (2.92% voltage drop) or 2/0 AWG aluminum (2.39% voltage drop).

Recommended Copper Wire
2 AWG
Voltage drop: 2.92% · 75°C rating: 115A
Recommended Aluminum Wire
2/0 AWG
Voltage drop: 2.39% · 75°C rating: 135A
Minimum Circular Mils (Cu)
64,500 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
2 AWG Copper
Copper Voltage Drop2.92%
Aluminum Alternative2/0 AWG
Aluminum Voltage Drop2.39%

Frequently Asked Questions — 30A · 300 ft (120V)

What size copper wire do I need for 30 amps at 300 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 2 AWG copper wire for a 30-amp, 300-foot one-way run at 120V. This produces an estimated 2.92% voltage drop.

Can I use aluminum wire for 30 amps at 300 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 30A at 300 ft (120V), step up to 2/0 AWG aluminum conductor (2.39% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 2 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 30 Amps (120V)

30A @ 25 ft30A @ 50 ft30A @ 75 ft30A @ 100 ft30A @ 125 ft30A @ 150 ft30A @ 200 ft30A @ 250 ft30A @ 300 ft30A @ 400 ft

Other Amperages at 300 Feet (120V)

15A @ 300 ft20A @ 300 ft30A @ 300 ft40A @ 300 ft50A @ 300 ft60A @ 300 ft70A @ 300 ft80A @ 300 ft100A @ 300 ft125A @ 300 ft150A @ 300 ft200A @ 300 ft