NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 30 Amps at 100 Feet (120V)?

For a 30-amp circuit running 100 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 6 AWG copper (2.46% voltage drop) or 4 AWG aluminum (2.54% voltage drop).

Recommended Copper Wire
6 AWG
Voltage drop: 2.46% · 75°C rating: 65A
Recommended Aluminum Wire
4 AWG
Voltage drop: 2.54% · 75°C rating: 65A
Minimum Circular Mils (Cu)
21,500 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
6 AWG Copper
Copper Voltage Drop2.46%
Aluminum Alternative4 AWG
Aluminum Voltage Drop2.54%

Frequently Asked Questions — 30A · 100 ft (120V)

What size copper wire do I need for 30 amps at 100 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 6 AWG copper wire for a 30-amp, 100-foot one-way run at 120V. This produces an estimated 2.46% voltage drop.

Can I use aluminum wire for 30 amps at 100 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 30A at 100 ft (120V), step up to 4 AWG aluminum conductor (2.54% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 6 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 30 Amps (120V)

30A @ 25 ft30A @ 50 ft30A @ 75 ft30A @ 100 ft30A @ 125 ft30A @ 150 ft30A @ 200 ft30A @ 250 ft30A @ 300 ft30A @ 400 ft

Other Amperages at 100 Feet (120V)

15A @ 100 ft20A @ 100 ft30A @ 100 ft40A @ 100 ft50A @ 100 ft60A @ 100 ft70A @ 100 ft80A @ 100 ft100A @ 100 ft125A @ 100 ft150A @ 100 ft200A @ 100 ft