NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 100 Amps at 100 Feet (120V)?

For a 100-amp circuit running 100 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 1 AWG copper (2.57% voltage drop) or 2/0 AWG aluminum (2.65% voltage drop).

Recommended Copper Wire
1 AWG
Voltage drop: 2.57% · 75°C rating: 130A
Recommended Aluminum Wire
2/0 AWG
Voltage drop: 2.65% · 75°C rating: 135A
Minimum Circular Mils (Cu)
71,667 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
1 AWG Copper
Copper Voltage Drop2.57%
Aluminum Alternative2/0 AWG
Aluminum Voltage Drop2.65%

Frequently Asked Questions — 100A · 100 ft (120V)

What size copper wire do I need for 100 amps at 100 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1 AWG copper wire for a 100-amp, 100-foot one-way run at 120V. This produces an estimated 2.57% voltage drop.

Can I use aluminum wire for 100 amps at 100 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 100A at 100 ft (120V), step up to 2/0 AWG aluminum conductor (2.65% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 100 Amps (120V)

100A @ 25 ft100A @ 50 ft100A @ 75 ft100A @ 100 ft100A @ 125 ft100A @ 150 ft100A @ 200 ft100A @ 250 ft100A @ 300 ft100A @ 400 ft

Other Amperages at 100 Feet (120V)

15A @ 100 ft20A @ 100 ft30A @ 100 ft40A @ 100 ft50A @ 100 ft60A @ 100 ft70A @ 100 ft80A @ 100 ft100A @ 100 ft125A @ 100 ft150A @ 100 ft200A @ 100 ft