What Size Wire for 100 Amps at 25 Feet (120V)?
For a 100-amp circuit running 25 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 3 AWG copper (1.02% voltage drop) or 1 AWG aluminum (1.06% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 100A · 25 ft (120V)
What size copper wire do I need for 100 amps at 25 feet (120V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 3 AWG copper wire for a 100-amp, 25-foot one-way run at 120V. This produces an estimated 1.02% voltage drop.
Can I use aluminum wire for 100 amps at 25 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 100A at 25 ft (120V), step up to 1 AWG aluminum conductor (1.06% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 3 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.