NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 40 Amps at 25 Feet (120V)?

For a 40-amp circuit running 25 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 8 AWG copper (1.3% voltage drop) or 8 AWG aluminum (2.14% voltage drop).

Recommended Copper Wire
8 AWG
Voltage drop: 1.3% · 75°C rating: 50A
Recommended Aluminum Wire
8 AWG
Voltage drop: 2.14% · 75°C rating: 40A
Minimum Circular Mils (Cu)
7,167 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
8 AWG Copper
Copper Voltage Drop1.3%
Aluminum Alternative8 AWG
Aluminum Voltage Drop2.14%

Frequently Asked Questions — 40A · 25 ft (120V)

What size copper wire do I need for 40 amps at 25 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 8 AWG copper wire for a 40-amp, 25-foot one-way run at 120V. This produces an estimated 1.3% voltage drop.

Can I use aluminum wire for 40 amps at 25 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 40A at 25 ft (120V), step up to 8 AWG aluminum conductor (2.14% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 8 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 40 Amps (120V)

40A @ 25 ft40A @ 50 ft40A @ 75 ft40A @ 100 ft40A @ 125 ft40A @ 150 ft40A @ 200 ft40A @ 250 ft40A @ 300 ft40A @ 400 ft

Other Amperages at 25 Feet (120V)

15A @ 25 ft20A @ 25 ft30A @ 25 ft40A @ 25 ft50A @ 25 ft60A @ 25 ft70A @ 25 ft80A @ 25 ft100A @ 25 ft125A @ 25 ft150A @ 25 ft200A @ 25 ft