NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 125 Amps at 25 Feet (120V)?

For a 125-amp circuit running 25 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 1 AWG copper (0.8% voltage drop) or 2/0 AWG aluminum (0.83% voltage drop).

Recommended Copper Wire
1 AWG
Voltage drop: 0.8% · 75°C rating: 130A
Recommended Aluminum Wire
2/0 AWG
Voltage drop: 0.83% · 75°C rating: 135A
Minimum Circular Mils (Cu)
22,396 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
1 AWG Copper
Copper Voltage Drop0.8%
Aluminum Alternative2/0 AWG
Aluminum Voltage Drop0.83%

Frequently Asked Questions — 125A · 25 ft (120V)

What size copper wire do I need for 125 amps at 25 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1 AWG copper wire for a 125-amp, 25-foot one-way run at 120V. This produces an estimated 0.8% voltage drop.

Can I use aluminum wire for 125 amps at 25 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 125A at 25 ft (120V), step up to 2/0 AWG aluminum conductor (0.83% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 125 Amps (120V)

125A @ 25 ft125A @ 50 ft125A @ 75 ft125A @ 100 ft125A @ 125 ft125A @ 150 ft125A @ 200 ft125A @ 250 ft125A @ 300 ft125A @ 400 ft

Other Amperages at 25 Feet (120V)