NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 80 Amps at 25 Feet (120V)?

For a 80-amp circuit running 25 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 4 AWG copper (1.03% voltage drop) or 2 AWG aluminum (1.06% voltage drop).

Recommended Copper Wire
4 AWG
Voltage drop: 1.03% · 75°C rating: 85A
Recommended Aluminum Wire
2 AWG
Voltage drop: 1.06% · 75°C rating: 90A
Minimum Circular Mils (Cu)
14,333 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4 AWG Copper
Copper Voltage Drop1.03%
Aluminum Alternative2 AWG
Aluminum Voltage Drop1.06%

Frequently Asked Questions — 80A · 25 ft (120V)

What size copper wire do I need for 80 amps at 25 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4 AWG copper wire for a 80-amp, 25-foot one-way run at 120V. This produces an estimated 1.03% voltage drop.

Can I use aluminum wire for 80 amps at 25 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 80A at 25 ft (120V), step up to 2 AWG aluminum conductor (1.06% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.