NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 80 Amps at 50 Feet (120V)?

For a 80-amp circuit running 50 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 4 AWG copper (2.06% voltage drop) or 2 AWG aluminum (2.13% voltage drop).

Recommended Copper Wire
4 AWG
Voltage drop: 2.06% · 75°C rating: 85A
Recommended Aluminum Wire
2 AWG
Voltage drop: 2.13% · 75°C rating: 90A
Minimum Circular Mils (Cu)
28,667 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4 AWG Copper
Copper Voltage Drop2.06%
Aluminum Alternative2 AWG
Aluminum Voltage Drop2.13%

Frequently Asked Questions — 80A · 50 ft (120V)

What size copper wire do I need for 80 amps at 50 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4 AWG copper wire for a 80-amp, 50-foot one-way run at 120V. This produces an estimated 2.06% voltage drop.

Can I use aluminum wire for 80 amps at 50 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 80A at 50 ft (120V), step up to 2 AWG aluminum conductor (2.13% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 80 Amps (120V)

80A @ 25 ft80A @ 50 ft80A @ 75 ft80A @ 100 ft80A @ 125 ft80A @ 150 ft80A @ 200 ft80A @ 250 ft80A @ 300 ft80A @ 400 ft

Other Amperages at 50 Feet (120V)

15A @ 50 ft20A @ 50 ft30A @ 50 ft40A @ 50 ft50A @ 50 ft60A @ 50 ft70A @ 50 ft80A @ 50 ft100A @ 50 ft125A @ 50 ft150A @ 50 ft200A @ 50 ft