What Size Wire for 80 Amps at 125 Feet (120V)?
For a 80-amp circuit running 125 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 1 AWG copper (2.57% voltage drop) or 2/0 AWG aluminum (2.65% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 80A · 125 ft (120V)
What size copper wire do I need for 80 amps at 125 feet (120V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1 AWG copper wire for a 80-amp, 125-foot one-way run at 120V. This produces an estimated 2.57% voltage drop.
Can I use aluminum wire for 80 amps at 125 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 80A at 125 ft (120V), step up to 2/0 AWG aluminum conductor (2.65% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.