NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 200 Amps at 125 Feet (120V)?

For a 200-amp circuit running 125 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 4/0 AWG copper (2.54% voltage drop) or 300 kcmil aluminum (2.94% voltage drop).

Recommended Copper Wire
4/0 AWG
Voltage drop: 2.54% · 75°C rating: 230A
Recommended Aluminum Wire
300 kcmil
Voltage drop: 2.94% · 75°C rating: 230A
Minimum Circular Mils (Cu)
179,167 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4/0 AWG Copper
Copper Voltage Drop2.54%
Aluminum Alternative300 kcmil
Aluminum Voltage Drop2.94%

Frequently Asked Questions — 200A · 125 ft (120V)

What size copper wire do I need for 200 amps at 125 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4/0 AWG copper wire for a 200-amp, 125-foot one-way run at 120V. This produces an estimated 2.54% voltage drop.

Can I use aluminum wire for 200 amps at 125 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 200A at 125 ft (120V), step up to 300 kcmil aluminum conductor (2.94% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 200 Amps (120V)

200A @ 25 ft200A @ 50 ft200A @ 75 ft200A @ 100 ft200A @ 125 ft200A @ 150 ft200A @ 200 ft200A @ 250 ft200A @ 300 ft200A @ 400 ft

Other Amperages at 125 Feet (120V)

15A @ 125 ft20A @ 125 ft30A @ 125 ft40A @ 125 ft50A @ 125 ft60A @ 125 ft70A @ 125 ft80A @ 125 ft100A @ 125 ft125A @ 125 ft150A @ 125 ft200A @ 125 ft