NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 200 Amps at 150 Feet (120V)?

For a 200-amp circuit running 150 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 250 kcmil copper (2.58% voltage drop) or 400 kcmil aluminum (2.65% voltage drop).

Recommended Copper Wire
250 kcmil
Voltage drop: 2.58% · 75°C rating: 255A
Recommended Aluminum Wire
400 kcmil
Voltage drop: 2.65% · 75°C rating: 270A
Minimum Circular Mils (Cu)
215,000 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
250 kcmil Copper
Copper Voltage Drop2.58%
Aluminum Alternative400 kcmil
Aluminum Voltage Drop2.65%

Frequently Asked Questions — 200A · 150 ft (120V)

What size copper wire do I need for 200 amps at 150 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 250 kcmil copper wire for a 200-amp, 150-foot one-way run at 120V. This produces an estimated 2.58% voltage drop.

Can I use aluminum wire for 200 amps at 150 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 200A at 150 ft (120V), step up to 400 kcmil aluminum conductor (2.65% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 250 kcmil keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 200 Amps (120V)

200A @ 25 ft200A @ 50 ft200A @ 75 ft200A @ 100 ft200A @ 125 ft200A @ 150 ft200A @ 200 ft200A @ 250 ft200A @ 300 ft200A @ 400 ft

Other Amperages at 150 Feet (120V)

15A @ 150 ft20A @ 150 ft30A @ 150 ft40A @ 150 ft50A @ 150 ft60A @ 150 ft70A @ 150 ft80A @ 150 ft100A @ 150 ft125A @ 150 ft150A @ 150 ft200A @ 150 ft