NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 150 Amps at 150 Feet (120V)?

For a 150-amp circuit running 150 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 3/0 AWG copper (2.88% voltage drop) or 300 kcmil aluminum (2.65% voltage drop).

Recommended Copper Wire
3/0 AWG
Voltage drop: 2.88% · 75°C rating: 200A
Recommended Aluminum Wire
300 kcmil
Voltage drop: 2.65% · 75°C rating: 230A
Minimum Circular Mils (Cu)
161,250 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
3/0 AWG Copper
Copper Voltage Drop2.88%
Aluminum Alternative300 kcmil
Aluminum Voltage Drop2.65%

Frequently Asked Questions — 150A · 150 ft (120V)

What size copper wire do I need for 150 amps at 150 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 3/0 AWG copper wire for a 150-amp, 150-foot one-way run at 120V. This produces an estimated 2.88% voltage drop.

Can I use aluminum wire for 150 amps at 150 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 150A at 150 ft (120V), step up to 300 kcmil aluminum conductor (2.65% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 3/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.