NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 150 Amps at 250 Feet (120V)?

For a 150-amp circuit running 250 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 300 kcmil copper (2.69% voltage drop) or 500 kcmil aluminum (2.65% voltage drop).

Recommended Copper Wire
300 kcmil
Voltage drop: 2.69% · 75°C rating: 285A
Recommended Aluminum Wire
500 kcmil
Voltage drop: 2.65% · 75°C rating: 310A
Minimum Circular Mils (Cu)
268,750 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
300 kcmil Copper
Copper Voltage Drop2.69%
Aluminum Alternative500 kcmil
Aluminum Voltage Drop2.65%

Frequently Asked Questions — 150A · 250 ft (120V)

What size copper wire do I need for 150 amps at 250 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 300 kcmil copper wire for a 150-amp, 250-foot one-way run at 120V. This produces an estimated 2.69% voltage drop.

Can I use aluminum wire for 150 amps at 250 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 150A at 250 ft (120V), step up to 500 kcmil aluminum conductor (2.65% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 300 kcmil keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.