What Size Wire for 50 Amps at 250 Feet (120V)?
For a 50-amp circuit running 250 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 1/0 AWG copper (2.54% voltage drop) or 3/0 AWG aluminum (2.63% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 50A · 250 ft (120V)
What size copper wire do I need for 50 amps at 250 feet (120V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1/0 AWG copper wire for a 50-amp, 250-foot one-way run at 120V. This produces an estimated 2.54% voltage drop.
Can I use aluminum wire for 50 amps at 250 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 50A at 250 ft (120V), step up to 3/0 AWG aluminum conductor (2.63% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.