NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 50 Amps at 300 Feet (120V)?

For a 50-amp circuit running 300 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 2/0 AWG copper (2.42% voltage drop) or 4/0 AWG aluminum (2.5% voltage drop).

Recommended Copper Wire
2/0 AWG
Voltage drop: 2.42% · 75°C rating: 175A
Recommended Aluminum Wire
4/0 AWG
Voltage drop: 2.5% · 75°C rating: 180A
Minimum Circular Mils (Cu)
107,500 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
2/0 AWG Copper
Copper Voltage Drop2.42%
Aluminum Alternative4/0 AWG
Aluminum Voltage Drop2.5%

Frequently Asked Questions — 50A · 300 ft (120V)

What size copper wire do I need for 50 amps at 300 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 2/0 AWG copper wire for a 50-amp, 300-foot one-way run at 120V. This produces an estimated 2.42% voltage drop.

Can I use aluminum wire for 50 amps at 300 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 50A at 300 ft (120V), step up to 4/0 AWG aluminum conductor (2.5% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 2/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.