NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 70 Amps at 100 Feet (120V)?

For a 70-amp circuit running 100 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 3 AWG copper (2.86% voltage drop) or 1 AWG aluminum (2.96% voltage drop).

Recommended Copper Wire
3 AWG
Voltage drop: 2.86% · 75°C rating: 100A
Recommended Aluminum Wire
1 AWG
Voltage drop: 2.96% · 75°C rating: 100A
Minimum Circular Mils (Cu)
50,167 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
3 AWG Copper
Copper Voltage Drop2.86%
Aluminum Alternative1 AWG
Aluminum Voltage Drop2.96%

Frequently Asked Questions — 70A · 100 ft (120V)

What size copper wire do I need for 70 amps at 100 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 3 AWG copper wire for a 70-amp, 100-foot one-way run at 120V. This produces an estimated 2.86% voltage drop.

Can I use aluminum wire for 70 amps at 100 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 70A at 100 ft (120V), step up to 1 AWG aluminum conductor (2.96% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 3 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.