NEC Table 310.16 (75°C) 120V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 70 Amps at 200 Feet (120V)?

For a 70-amp circuit running 200 feet (one-way) at 120 volts keeping voltage drop within the NEC-recommended 3% limit, use 1/0 AWG copper (2.85% voltage drop) or 3/0 AWG aluminum (2.95% voltage drop).

Recommended Copper Wire
1/0 AWG
Voltage drop: 2.85% · 75°C rating: 150A
Recommended Aluminum Wire
3/0 AWG
Voltage drop: 2.95% · 75°C rating: 155A
Minimum Circular Mils (Cu)
100,333 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
1/0 AWG Copper
Copper Voltage Drop2.85%
Aluminum Alternative3/0 AWG
Aluminum Voltage Drop2.95%

Frequently Asked Questions — 70A · 200 ft (120V)

What size copper wire do I need for 70 amps at 200 feet (120V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1/0 AWG copper wire for a 70-amp, 200-foot one-way run at 120V. This produces an estimated 2.85% voltage drop.

Can I use aluminum wire for 70 amps at 200 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 70A at 200 ft (120V), step up to 3/0 AWG aluminum conductor (2.95% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 70 Amps (120V)

70A @ 25 ft70A @ 50 ft70A @ 75 ft70A @ 100 ft70A @ 125 ft70A @ 150 ft70A @ 200 ft70A @ 250 ft70A @ 300 ft70A @ 400 ft

Other Amperages at 200 Feet (120V)

15A @ 200 ft20A @ 200 ft30A @ 200 ft40A @ 200 ft50A @ 200 ft60A @ 200 ft70A @ 200 ft80A @ 200 ft100A @ 200 ft125A @ 200 ft150A @ 200 ft200A @ 200 ft