NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 200 Amps at 400 Feet (240V)?

For a 200-amp circuit running 400 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 300 kcmil copper (2.87% voltage drop) or 500 kcmil aluminum (2.83% voltage drop).

Recommended Copper Wire
300 kcmil
Voltage drop: 2.87% · 75°C rating: 285A
Recommended Aluminum Wire
500 kcmil
Voltage drop: 2.83% · 75°C rating: 310A
Minimum Circular Mils (Cu)
286,667 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
300 kcmil Copper
Copper Voltage Drop2.87%
Aluminum Alternative500 kcmil
Aluminum Voltage Drop2.83%

Frequently Asked Questions — 200A · 400 ft (240V)

What size copper wire do I need for 200 amps at 400 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 300 kcmil copper wire for a 200-amp, 400-foot one-way run at 240V. This produces an estimated 2.87% voltage drop.

Can I use aluminum wire for 200 amps at 400 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 200A at 400 ft (240V), step up to 500 kcmil aluminum conductor (2.83% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 300 kcmil keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 200 Amps (240V)

200A @ 25 ft200A @ 50 ft200A @ 75 ft200A @ 100 ft200A @ 125 ft200A @ 150 ft200A @ 200 ft200A @ 250 ft200A @ 300 ft200A @ 400 ft

Other Amperages at 400 Feet (240V)

15A @ 400 ft20A @ 400 ft30A @ 400 ft40A @ 400 ft50A @ 400 ft60A @ 400 ft70A @ 400 ft80A @ 400 ft100A @ 400 ft125A @ 400 ft150A @ 400 ft200A @ 400 ft