What Size Wire for 125 Amps at 400 Feet (240V)?
For a 125-amp circuit running 400 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 4/0 AWG copper (2.54% voltage drop) or 300 kcmil aluminum (2.94% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 125A · 400 ft (240V)
What size copper wire do I need for 125 amps at 400 feet (240V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4/0 AWG copper wire for a 125-amp, 400-foot one-way run at 240V. This produces an estimated 2.54% voltage drop.
Can I use aluminum wire for 125 amps at 400 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 125A at 400 ft (240V), step up to 300 kcmil aluminum conductor (2.94% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.