NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 125 Amps at 200 Feet (240V)?

For a 125-amp circuit running 200 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 1/0 AWG copper (2.54% voltage drop) or 3/0 AWG aluminum (2.63% voltage drop).

Recommended Copper Wire
1/0 AWG
Voltage drop: 2.54% · 75°C rating: 150A
Recommended Aluminum Wire
3/0 AWG
Voltage drop: 2.63% · 75°C rating: 155A
Minimum Circular Mils (Cu)
89,583 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
1/0 AWG Copper
Copper Voltage Drop2.54%
Aluminum Alternative3/0 AWG
Aluminum Voltage Drop2.63%

Frequently Asked Questions — 125A · 200 ft (240V)

What size copper wire do I need for 125 amps at 200 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1/0 AWG copper wire for a 125-amp, 200-foot one-way run at 240V. This produces an estimated 2.54% voltage drop.

Can I use aluminum wire for 125 amps at 200 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 125A at 200 ft (240V), step up to 3/0 AWG aluminum conductor (2.63% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1/0 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.