What Size Wire for 80 Amps at 200 Feet (240V)?
For a 80-amp circuit running 200 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 2 AWG copper (2.59% voltage drop) or 1/0 AWG aluminum (2.68% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 80A · 200 ft (240V)
What size copper wire do I need for 80 amps at 200 feet (240V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 2 AWG copper wire for a 80-amp, 200-foot one-way run at 240V. This produces an estimated 2.59% voltage drop.
Can I use aluminum wire for 80 amps at 200 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 80A at 200 ft (240V), step up to 1/0 AWG aluminum conductor (2.68% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 2 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.