NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 80 Amps at 75 Feet (240V)?

For a 80-amp circuit running 75 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 4 AWG copper (1.55% voltage drop) or 2 AWG aluminum (1.6% voltage drop).

Recommended Copper Wire
4 AWG
Voltage drop: 1.55% · 75°C rating: 85A
Recommended Aluminum Wire
2 AWG
Voltage drop: 1.6% · 75°C rating: 90A
Minimum Circular Mils (Cu)
21,500 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
4 AWG Copper
Copper Voltage Drop1.55%
Aluminum Alternative2 AWG
Aluminum Voltage Drop1.6%

Frequently Asked Questions — 80A · 75 ft (240V)

What size copper wire do I need for 80 amps at 75 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 4 AWG copper wire for a 80-amp, 75-foot one-way run at 240V. This produces an estimated 1.55% voltage drop.

Can I use aluminum wire for 80 amps at 75 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 80A at 75 ft (240V), step up to 2 AWG aluminum conductor (1.6% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 4 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 80 Amps (240V)

80A @ 25 ft80A @ 50 ft80A @ 75 ft80A @ 100 ft80A @ 125 ft80A @ 150 ft80A @ 200 ft80A @ 250 ft80A @ 300 ft80A @ 400 ft

Other Amperages at 75 Feet (240V)

15A @ 75 ft20A @ 75 ft30A @ 75 ft40A @ 75 ft50A @ 75 ft60A @ 75 ft70A @ 75 ft80A @ 75 ft100A @ 75 ft125A @ 75 ft150A @ 75 ft200A @ 75 ft