NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 30 Amps at 75 Feet (240V)?

For a 30-amp circuit running 75 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 10 AWG copper (2.33% voltage drop) or 8 AWG aluminum (2.41% voltage drop).

Recommended Copper Wire
10 AWG
Voltage drop: 2.33% · 75°C rating: 30A
Recommended Aluminum Wire
8 AWG
Voltage drop: 2.41% · 75°C rating: 40A
Minimum Circular Mils (Cu)
8,063 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
10 AWG Copper
Copper Voltage Drop2.33%
Aluminum Alternative8 AWG
Aluminum Voltage Drop2.41%

Frequently Asked Questions — 30A · 75 ft (240V)

What size copper wire do I need for 30 amps at 75 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 10 AWG copper wire for a 30-amp, 75-foot one-way run at 240V. This produces an estimated 2.33% voltage drop.

Can I use aluminum wire for 30 amps at 75 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 30A at 75 ft (240V), step up to 8 AWG aluminum conductor (2.41% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 10 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 30 Amps (240V)

30A @ 25 ft30A @ 50 ft30A @ 75 ft30A @ 100 ft30A @ 125 ft30A @ 150 ft30A @ 200 ft30A @ 250 ft30A @ 300 ft30A @ 400 ft

Other Amperages at 75 Feet (240V)

15A @ 75 ft20A @ 75 ft30A @ 75 ft40A @ 75 ft50A @ 75 ft60A @ 75 ft70A @ 75 ft80A @ 75 ft100A @ 75 ft125A @ 75 ft150A @ 75 ft200A @ 75 ft