NEC Table 310.16 (75°C) 240V Single-Phase ≤ 3% Voltage Drop Rule

What Size Wire for 50 Amps at 300 Feet (240V)?

For a 50-amp circuit running 300 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 2 AWG copper (2.43% voltage drop) or 1/0 AWG aluminum (2.51% voltage drop).

Recommended Copper Wire
2 AWG
Voltage drop: 2.43% · 75°C rating: 115A
Recommended Aluminum Wire
1/0 AWG
Voltage drop: 2.51% · 75°C rating: 120A
Minimum Circular Mils (Cu)
53,750 CM
Single-phase formula: 2 × K × I × D / ΔV

Interactive NEC Wire Gauge & Voltage Drop Calculator

Live NEC Result
2 AWG Copper
Copper Voltage Drop2.43%
Aluminum Alternative1/0 AWG
Aluminum Voltage Drop2.51%

Frequently Asked Questions — 50A · 300 ft (240V)

What size copper wire do I need for 50 amps at 300 feet (240V)?

Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 2 AWG copper wire for a 50-amp, 300-foot one-way run at 240V. This produces an estimated 2.43% voltage drop.

Can I use aluminum wire for 50 amps at 300 feet?

Yes, if terminals and breakers are dual-rated (CU/AL). For 50A at 300 ft (240V), step up to 1/0 AWG aluminum conductor (2.51% voltage drop) to match copper's conductivity.

Why does distance in feet change the required AWG wire gauge?

Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 2 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.

Other Distances for 50 Amps (240V)

50A @ 25 ft50A @ 50 ft50A @ 75 ft50A @ 100 ft50A @ 125 ft50A @ 150 ft50A @ 200 ft50A @ 250 ft50A @ 300 ft50A @ 400 ft

Other Amperages at 300 Feet (240V)

15A @ 300 ft20A @ 300 ft30A @ 300 ft40A @ 300 ft50A @ 300 ft60A @ 300 ft70A @ 300 ft80A @ 300 ft100A @ 300 ft125A @ 300 ft150A @ 300 ft200A @ 300 ft