What Size Wire for 70 Amps at 300 Feet (240V)?
For a 70-amp circuit running 300 feet (one-way) at 240 volts keeping voltage drop within the NEC-recommended 3% limit, use 1 AWG copper (2.7% voltage drop) or 2/0 AWG aluminum (2.79% voltage drop).
Interactive NEC Wire Gauge & Voltage Drop Calculator
Frequently Asked Questions — 70A · 300 ft (240V)
What size copper wire do I need for 70 amps at 300 feet (240V)?
Per NEC Table 310.16 (75°C) and the 3% voltage drop rule, use 1 AWG copper wire for a 70-amp, 300-foot one-way run at 240V. This produces an estimated 2.7% voltage drop.
Can I use aluminum wire for 70 amps at 300 feet?
Yes, if terminals and breakers are dual-rated (CU/AL). For 70A at 300 ft (240V), step up to 2/0 AWG aluminum conductor (2.79% voltage drop) to match copper's conductivity.
Why does distance in feet change the required AWG wire gauge?
Longer cable runs increase conductor resistance, causing voltage drop. Even if a thinner wire meets NEC ampacity limits, stepping up to 1 AWG keeps voltage drop under 3% so motors, EV chargers, and appliances run safely without overheating.